Operating Instructions – MOVIFIT® basic
6
Parameter directory of the MOVIFIT
®
basic inverter
Startup
6.8.2 Advanced parameters
The following table shows the advanced parameters:
No. Name Section Standard Description
P2-02 Speed n2 -P1-01 – +P1-01 10 Hz The drive runs with the speed that
was selected by the higher-level
controller.
P2-03 Speed n3 -P1-01 – +P1-01 25 Hz
P2-04 Speed n4 -P1-01 – +P1-01 50 Hz
P2-16 Zero speed holding
time
0 – 60 s 0.2 s Time during which the speed "0" is
held at the output before the drive is
inhibited.
P2-19 Keypad restart mode 0: Minimum speed 0 Speed selection when drive is
restarted.
1: Most recently used
speed
P2-21 Scaling factor 0.000 – 30.000 0.000 Scaling factor of the display
variable P2-22:
With P2-21 = "0", the display
function is deactivated.
P2-22 Display variable 1: Motor speed 1 Selection of variables displayed by
the unit.
This variable is scaled with
parameter P2-21.
2: Motor torque
3: Motor current
P2-24 Effective switching
frequency
4 kHz 16 kHz Effective switching frequency of the
power section.
A higher switching frequency
means less motor noise, but also
higher energy losses in the power
section.
8 kHz
16 kHz
P2-38 Parameter lock 0: Enabled 0 Blocking/enabling parameter
changes.
When the lock is active, you cannot
change any parameters.
1: Disabled
P2-39 Operating hours
counter
0 – 99999 hours Display Total number of operating hours of
the drive.
P2-40 Inverter power – Display Display of the power of
MOVIFIT
®
basic.