40
Operating Instructions – MOVIFIT® basic
6
Assigning the AS-Interface slave address
Startup
3. Make sure that the motor cannot start
e.g. by unplugging the motor connector(s) from the MOVIFIT
®
basic unit.
4. Set the AS-Interface slave address of the MOVIFIT
®
basic unit (only for MOVIFIT
®
basic with AS-Interface).
See chapter "Assigning the AS-Interface address" (page 40).
5. Start up the higher-level controller.
6. Plug in the motor connector(s) at MOVIFIT
®
basic.
7. Switch on the line voltage.
You can now control the MOVIFIT
®
basic drive with the higher-level controller (via binary
signals or AS-Interface).
6.5 Assigning the AS-Interface slave address
SEW-EURODRIVE supplies MOVIFIT
®
basic with AS-Interface with address 0.
You have the following options for assigning the AS-Interface address of MOVIFIT
®
basic (address 1 - 31):
Addresses are assigned automatically within a configured AS-Interface system
when replacing a MOVIFIT
®
basic drive.
The following prerequisites must be fulfilled:
–The new MOVIFIT
®
basic drive must have address 0.
If you need to replace multiple MOVIFIT
®
basic drives, you must exchange them
individually (one after another).
Manual address assignment via the plant master
Connect the drives to the AS-Interface cable one after another. Doing so prevents
several MOVIFIT
®
basic drives being assigned the same AS-Interface address.
Manual address assignment using a hand-held AS-Interface programming
device.
Observe the notes in the following section when connecting the MOVIFIT
®
basic
drive to the AS-Interface cable.
00
I