62
Operating Instructions – MOVIFIT® basic
7
Manual mode with LT-BG keypad
Operation
7.6 Manual mode with LT-BG keypad
(only for MOVIFIT
®
basic inverter)
7.6.1 Manual mode activation (parameter P1-12)
Proceed as follows to activate manual mode:
1. Set parameter P1-12
• to "1" => CW operation only
• or to "2" => CW and CCW operation
2. Enable the drive via the higher-level controller.
•For MOVIFIT
®
basic with binary control: DI0 and DI1 = "0"!
•For MOVIFIT
®
basic with AS-Interface: DO0 and DO1 = "0"!
7.6.2 Manual operation of MOVIFIT
®
basic inverter
The following functions of the MOVIFIT
®
basic inverter can be executed in manual
mode:
Enabling the drive Use the key to enable the drive.
With a setpoint speed ≠ "0", the drive will start.
Changing the setpoint
speed
Use the key and the key to set the required setpoint
speed.
The drive follows the setpoint speed.
Changing the direc-
tion of rotation
Use the key to change the direction of rotation.
Prerequisite: P1-12 = "2" (enable CW and CCW operation)
Stop the drive Use the key to stop the drive.
The drive brakes with the deceleration ramp (P1-04) to a stand-
still.
Starting the drive
(with setpoint speed)
At standstill, press the key and use the key and the
key to select the required setpoint speed.
Press the key to confirm your selection.
Then use the key to start the drive.
The drive accelerates with the acceleration ramp (P1-03) until it
reaches the target speed.
Resetting an error If an error occurs during manual operation, the display shows the
corresponding error message.
Eliminate the cause of the error.
Use the key to reset the error.
After the fault reset, manual operation remains active.