7SR210 Settings Guide
Unrestricted Page 30 of 61 © 2018 Siemens Protection Devices Limited
Description Range Default
E10 Pickup Delay
Time before equation output operates, after equation satisfied
0, 0.01 ... 14300, 14400 0 s
E10 Dropoff Delay
Time before equation output resets, after equation nolonger satisfied
0, 0.01 ... 14300, 14400 0 s
E10 Counter Target
Select number of times equation must be satisfied before equation
output operates
1, 2 ... 998, 999 1
E10 Counter Reset Mode
Select type of counter reset mode
Off, Multi-shot, Single-shot Off
E10 Counter Reset Time
Select counter reset time
0, 0.01 ... 14300, 14400 0 s
E11 Equation
Enable or Disable logic equation E11
Disabled, Enabled Disabled
E11
Specify logic equations of the form En =
<Operand><Operator><Operand>using the
following:0123456789=Digit() = Parenthesis! = NOT operation. =
AND operation^ = EXCLUSIVE OR operationE(followed by a digit) =
Equation numberF (Followed by a digit) = Function Key
numberI(Followed by a digit) = Binary Input numberL(Followed by a
digit) = LED numberO(Followed by a digit) = output relay
numberV(Followed by a digit) =Virtual Input/Output
number.ExamplesMake a function key LED toggle when function key
is pressed (requires E1 to drive L11 in output matrix)E1 =
F3^L11
(20 Character String)
E11 Pickup Delay
Time before equation output operates, after equation satisfied
0, 0.01 ... 14300, 14400 0 s
E11 Dropoff Delay
Time before equation output resets, after equation nolonger satisfied
0, 0.01 ... 14300, 14400 0 s
E11 Counter Target
Select number of times equation must be satisfied before equation
output operates
1, 2 ... 998, 999 1
E11 Counter Reset Mode
Select type of counter reset mode
Off, Multi-shot, Single-shot Off
E11 Counter Reset Time
Select counter reset time
0, 0.01 ... 14300, 14400 0 s
E12 Equation
Enable or Disable logic equation E12
Disabled, Enabled Disabled
E12
Specify logic equations of the form En =
<Operand><Operator><Operand>using the
following:0123456789=Digit() = Parenthesis! = NOT operation. =
AND operation^ = EXCLUSIVE OR operationE(followed by a digit) =
Equation numberF (Followed by a digit) = Function Key
numberI(Followed by a digit) = Binary Input numberL(Followed by a
digit) = LED numberO(Followed by a digit) = output relay
numberV(Followed by a digit) =Virtual Input/Output
number.ExamplesMake a function key LED toggle when function key
is pressed (requires E1 to drive L11 in output matrix)E1 =
F3^L11
(20 Character String)
E12 Pickup Delay
Time before equation output operates, after equation satisfied
0, 0.01 ... 14300, 14400 0 s
E12 Dropoff Delay
Time before equation output resets, after equation nolonger satisfied
0, 0.01 ... 14300, 14400 0 s
E12 Counter Target
Select number of times equation must be satisfied before equation
output operates
1, 2 ... 998, 999 1