7SR210 Settings Guide
Unrestricted ©2018 Siemens Protection Devices Limited Page 31 of 61
Description Range Default
E12 Counter Reset Mode
Select type of counter reset mode
Off, Multi-shot, Single-shot Off
E12 Counter Reset Time
Select counter reset time
0, 0.01 ... 14300, 14400 0 s
E13 Equation
Enable or Disable logic equation E13
Disabled, Enabled Disabled
E13
Specify logic equations of the form En =
<Operand><Operator><Operand>using the
following:0123456789=Digit() = Parenthesis! = NOT operation. =
AND operation^ = EXCLUSIVE OR operationE(followed by a digit) =
Equation numberF (Followed by a digit) = Function Key
numberI(Followed by a digit) = Binary Input numberL(Followed by a
digit) = LED numberO(Followed by a digit) = output relay
numberV(Followed by a digit) =Virtual Input/Output
number.ExamplesMake a function key LED toggle when function key
is pressed (requires E1 to drive L11 in output matrix)E1 =
F3^L11
(20 Character String)
E13 Pickup Delay
Time before equation output operates, after equation satisfied
0, 0.01 ... 14300, 14400 0 s
E13 Dropoff Delay
Time before equation output resets, after equation nolonger satisfied
0, 0.01 ... 14300, 14400 0 s
E13 Counter Target
Select number of times equation must be satisfied before equation
output operates
1, 2 ... 998, 999 1
E13 Counter Reset Mode
Select type of counter reset mode
Off, Multi-shot, Single-shot Off
E13 Counter Reset Time
Select counter reset time
0, 0.01 ... 14300, 14400 0 s
E14 Equation
Enable or Disable logic equation E14
Disabled, Enabled Disabled
E14
Specify logic equations of the form En =
<Operand><Operator><Operand>using the
following:0123456789=Digit() = Parenthesis! = NOT operation. =
AND operation^ = EXCLUSIVE OR operationE(followed by a digit) =
Equation numberF (Followed by a digit) = Function Key
numberI(Followed by a digit) = Binary Input numberL(Followed by a
digit) = LED numberO(Followed by a digit) = output relay
numberV(Followed by a digit) =Virtual Input/Output
number.ExamplesMake a function key LED toggle when function key
is pressed (requires E1 to drive L11 in output matrix)E1 =
F3^L11
(20 Character String)
E14 Pickup Delay
Time before equation output operates, after equation satisfied
0, 0.01 ... 14300, 14400 0 s
E14 Dropoff Delay
Time before equation output resets, after equation nolonger satisfied
0, 0.01 ... 14300, 14400 0 s
E14 Counter Target
Select number of times equation must be satisfied before equation
output operates
1, 2 ... 998, 999 1
E14 Counter Reset Mode
Select type of counter reset mode
Off, Multi-shot, Single-shot Off
E14 Counter Reset Time
Select counter reset time
0, 0.01 ... 14300, 14400 0 s
E15 Equation
Enable or Disable logic equation E15
Disabled, Enabled Disabled