7SR220 Technical Manual
Chapter 4 - Page 66 of 96 © 2017 Siemens Protection Devices Limited
Binary Input Points
Static (Steady-State) Object Number: 1 (Packed Format)
Change Event Object Number: 1 (w/o Time)
Static Variation reported when variation 0 requested: 1 (Binary Input w/o status)
or 2 (Binary Input with status)
Change Event Variation reported when variation 0 requested: 1 (Binary Input Change w/o Time)
or 2 (Binary Input Change with Absolute Time)
or 3 (Binary Input Change with Relative Time)
Point
Index
Description
Default Change Event
Assigned Class (1,
2, 3 or none)
Default Variation
Static Object 1
Default Variation
Event Object 2
275 37-PhB 0,2 2 2
276 37-PhC 0,2 2 2
283 50BF-PhA 0,2 2 2
284 50BF-PhB 0,2 2 2
285 50BF-PhC 0,2 2 2
286 50BF-EF 0,2 2 2
287 79 Last Trip Lockout 0,2 2 2
288 60 CTS-I-PhA 0,2 2 2
289 60 CTS-I-PhB 0,2 2 2
290 60 CTS-I-PhC 0,2 2 2
291 Trip PhA 0,2 2 2
292 Trip PhB 0,2 2 2
293 Trip PhC 0,2 2 2
302 27/59 PhA 0,2 2 2
303 27/59 PhB 0,2 2 2
304 27/59 PhC 0,2 2 2
310 General Alarm 13 0,2 2 2
311 General Alarm 14 0,2 2 2
312 General Alarm 15 0,2 2 2
313 General Alarm 16 0,2 2 2
314 General Alarm 17 0,2 2 2
315 General Alarm 18 0,2 2 2
316 General Alarm 19 0,2 2 2
317 General Alarm 20 0,2 2 2
330 32-1 0,2 2 2
331 32-2 0,2 2 2
332 32S-1 0,2 2 2
333 32S-2 0,2 2 2
334 55-1 0,2 2 2
335 55-2 0,2 2 2
373 37SEF-1 0,2 2 2
374 37SEF-2 0,2 2 2
387 25 System Split 0,2 2 2
388 25 Live Line 0,2 2 2
389 25 Live Bus 0,2 2 2
390 25 Line U/V 0,2 2 2
391 25 Bus U/V 0,2 2 2
392 25 Voltage Dif > 0,2 2 2
393 25 CS Slip Freq > 0,2 2 2
394 25 SS Slip Freq > 0,2 2 2
395 25 COZ Slip Freq > 0,2 2 2
396 25 In Sync 0,2 2 2