Chapter 4 - Data Communications Definitions
© 2017 Siemens Protection Devices Limited Chapter 4 - Page 67 of 96
Binary Input Points
Static (Steady-State) Object Number: 1 (Packed Format)
Change Event Object Number: 1 (w/o Time)
Static Variation reported when variation 0 requested: 1 (Binary Input w/o status)
or 2 (Binary Input with status)
Change Event Variation reported when variation 0 requested: 1 (Binary Input Change w/o Time)
or 2 (Binary Input Change with Absolute Time)
or 3 (Binary Input Change with Relative Time)
Point
Index
Description
Default Change Event
Assigned Class (1,
2, 3 or none)
Default Variation
Static Object 1
Default Variation
Event Object 2
397 25 CS In Progress 0,2 2 2
398 25 SS In Progress 0,2 2 2
399 25 COZ In Progress 0,2 2 2
400 25 System Split LO 0,2 2 2
401 60VTF-Bus 0,2 2 2
411 Setting G1 selected 0,2 2 2
412 Setting G2 selected 0,2 2 2
413 Setting G3 selected 0,2 2 2
414 Setting G4 selected 0,2 2 2
415 Setting G5 selected 0,2 2 2
416 Setting G6 selected 0,2 2 2
417 Setting G7 selected 0,2 2 2
418 Setting G8 selected 0,2 2 2
420 79 AR In progress 0,2 2 2
422 HotLine Working 0,2 2 2
425 Inst Protection Out 0,2 2 2
427 CB 1 0,2 2 2
434 Man Override Sync 0,2 2 2
435 79 Override Sync 0,2 2 2
501 Virtual Input 1 0,2 2 2
502 Virtual Input 2 0,2 2 2
503 Virtual Input 3 0,2 2 2
504 Virtual Input 4 0,2 2 2
505 Virtual Input 5 0,2 2 2
506 Virtual Input 6 0,2 2 2
507 Virtual Input 7 0,2 2 2
508 Virtual Input 8 0,2 2 2
509 Virtual Input 9 0,2 2 2
510 Virtual Input 10 0,2 2 2
511 Virtual Input 11 0,2 2 2
512 Virtual Input 12 0,2 2 2
513 Virtual Input 13 0,2 2 2
514 Virtual Input 14 0,2 2 2
515 Virtual Input 15 0,2 2 2
516 Virtual Input 16 0,2 2 2
601 LED 1 0,2 2 2
602 LED 2 0,2 2 2
603 LED 3 0,2 2 2
604 LED 4 0,2 2 2
605 LED 5 0,2 2 2
606 LED 6 0,2 2 2