Chapter 4 - Data Communications Definitions
© 2017 Siemens Protection Devices Limited Chapter 4 - Page 75 of 96
Pulse On
Latch On
Close
Pulse On
Latch On
Close
Pulse On
Pulse On
Binary Output Status Points
Static (Steady-State) Object Number: 10
Change Event Object Number: 11
Control Relay Output Blocks (CROB) Object Number: 12
Binary Output Command Event Object Number: 13
Static Variation reported when variation 0 requested: 1 (Binary Output w/o status)
or 2 (Binary Output with status)
Change Event Variation reported when variation 0 requested: 1 (Binary Output Event w/o Time)
or 2 (Binary Output Event with Time)
Command Event Variation reported when variation 0 requested: 1 (Command Status w/o Time)
or 2 (Command Status with Time)
Point
Description
Index
Default
Change
Event
Assigned
Class
(1, 2, 3
or none)
Default
Variation
Static
Object 10
Default
Variation
Event
Object 11
Default
Command
Event
Object 13
Assigned
Class
(1, 2, 3
or none)
Default
Variation
Command
Event
Object 13
CROB
Supported
Operations
Default
CROB
Operations
90 Local mode 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
91 Local & Remote 0 2 2 0 1
Pulse On
Latch On Pulse On
Close
Pulse On
Pulse Off Pulse On
92 Man Override Sync on/off 0 2 2 0 1
Latch On
Latch Off
Pulse Off
Latch On
Close Latch Off
Trip
93 79 Override Sync on/off 0 2 2 0 1
Pulse On
Pulse Off
Latch On
Latch Off
Close
Trip
Pulse On
Pulse Off
Latch On
Latch Off
94
Reset CB Phase A Trip
Count, write only location.
0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
95
Reset CB Phase B Trip
Count, write only location.
0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
96
Reset CB Phase C Trip
Count, write only location.
0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
97
Reset CB EF Trip Count,
write only location.
0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
98 Reset Start Count (Action) 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
Latch On
99 User SP Command 1. 0 2 2 0 1
Pulse On
Latch On Pulse On
Close
Pulse On
100 User SP Command 2. 0 2 2 0 1 Latch On Pulse On
Close
101 User SP Command 3. 0 2 2 0 1
102 User SP Command 4. 0 2 2 0 1