Installation
Accessories
6
A6V10421795_en--_k
53 | 151
T
Participant with RS232 interface
RS485
PIN
Designation
Description
4
RS485_A
Line A
3
RS485_B
Line B
2
-
Not connected
1
-
Not connected
Admissible cable cross-section: 0.2…1.5 mm²
T1
First participant
Tn
Last participant
*) Stub lines must not exceed 20 m!
Do not forget about the polarity A, B!
Up to eight participants are allowed.
Terminate the line after the last participant with 120 Ω!
Use shielded cables.
Configuration:
The participant address and communication trouble setting can be configured in
FC360 Panel Configurator’. See document A6V10450595 for more details. Other
parameter settings are not configurable.
X3
6
5
7
8
RTS
TXD
DTR
RXD
0 V
CTS
DSR
DCD
DTE-HOST
T
1
2
3
4
3
4
X2
RS485_B
RS485_A
T1
Tn
2
1
*)
A
B
RS485 module