EasyManua.ls Logo

Siemens FC361 Series - Page 54

Siemens FC361 Series
151 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6
54 | 151
A6V10421795_en--_k
6.11.5.1 Event printer
The RS232 module connects one external printer Fujitsu DL3750+ to the panel.
Detailed information on the printer is available on the CD supplied with the printer.
Connection:
Precondition: RS232 module is installed. See chapter 'RS232/RS485 module
[➙ 52]'.
The picture below shows the connection between the printer and panel.
The connection cable is wired as per the following connection diagram.
The connection cable has a maximum length of 15 meters.
Use shielded cables.
FCA2001-A1
DB-25, male
A:
Screw connection on RS232 module (FCA2001-A1)
B:
25-pole connector (DB-25, male) for Fujitsu DL3750+ printer
Configuration:
No configuration is required.
FUJITSU DL3750+
FCA2001-A1
FC361-xx
X3
6
5
7
8
RTS
TXD
DTR
RXD
0 V
CTS
DSR
DCD
DTE-HOST
1
2
3
4
TXD
RXD
GND
B
A

Table of Contents