Operation
Operations under access level 2
8
A6V10421795_en--_k
83 | 151
3. Select 'Event log' and press . The 'Event log' window is open.
Event log L2
1 - Show log
2 - Advanced
4. Select 'Advanced' and press . The 'Advanced' window is open.
Advanced L2
Type: All
Start time: 08-01-2015
End time: 08-01-2015
Print:
Query
5. Select 'Type:', enter 'Start time:'/'End time:', and then select 'Query' and press
. All filtered events are displayed. Scroll by using / .
Rec. 001 of 008 L2
+ Short
Monitored output
Output card 4M
Circuit 02
03-01-2020 18:08:08
Explanation to number on the top line 'Record XXX of YYY':
XXX: Serial number of event, the first event is '001', the last event is 'YYY'.
YYY: Total number of all events.
For detailed information about the LCD display, see 'Event views [➙ 66]'.
To print filtered events, select 'Print:' with '√' in step 4.
8.5.3.2 Viewing compensation values
A compensation value in compensation logs/reports indicates dirt/dust level in
chamber of smoke detector OP720, OH720, OOH740, OOHC740, OP360 or
OH360. If it becomes larger, it means:
The detector chamber is dirtier.
The band of detection range is smaller.
The possibility of initiating false fire detection is higher.
In order to avoid false fire detection due to chamber dust level, note the following
compensation value range: