8
84 | 151
A6V10421795_en--_k
Compensation value
Indication
0 ~ 50
The dirt level is within a normal range.
50 ~ 80
Pay attention to value change.
80 ~ 120
Detector exchange is recommended.
150
Exchange the detector.
All compensation values are stored in the panel. You can view them one by one on
the local panel or view them all in a PC after uploading. See 'Backing up
compensation values to the PC [➙ 118]' for more information about viewing
compensation values from a PC.
To view compensation values from the panel
1. Press on the keypad. The 'Main menu' window is open.
Main menu L2
1 - System status
2 - Operation
3 - Event memory
4 - Login
5 - Lamp test
7 - Logout
2. Select 'Event memory' and press . The 'Event memory' window is open.
Event memory L2
1 - Event log
3 - Compensation Value
3. Select 'Compensation Value' and press . The 'Compensation Value' window is
open.
Compensation Value L2
1 - Show log
4. Select 'Show log' and press . The detailed compensation log appears on the
screen.
Device IDs in compensation value logs are only visible under access level 3 or
above.