Data blocks / error lists
C.4 Error classes
FM 352 electronic cam controller
Operating Instructions, 05/2011, A5E01071724-03
197
No. Meaning Diagnostic
interrupt
Internal module power supply failed
Cause Error in the FM 352
Effect
Module is reset
Provided that after resetting the module, no module
defect is detected, the module is ready for operation
again.
52
Remedy Replace the FM 352
Yes
Hardware interrupt lost
Cause A hardware interrupt event detected by FM 352 cannot be
reported, because the same event has not yet been
processed by the user program/CPU.
Effect
Cam processing will be deactivated
Track outputs will be disabled
With incremental encoders, synchronization is
canceled
70
Remedy
Link OB40 into the user program
Check the bus connection of the module
Deactivate hardware interrupt
Adapt your hardware and software to suit your
process requirements (for example, faster CPU,
optimize user program).
Yes
Encoder wire break
Cause
Encoder cable cut or not plugged in
Encoder has no transverse signals
Incorrect pin assignment
Cable length too long
Encoder signals short-circuited
Effect
Cam processing will be deactivated
Track outputs will be disabled
With incremental encoders, synchronization is
canceled
144
Remedy
Check the encoder cable
Keep within encoder specifications
Monitoring can be temporarily disabled using the
parameter assignment interface, but at the
responsibility of the operator.
Keep to the module's technical data