Commissioning the FM 352
FM 352 electronic cam controller
Operating Instructions, 05/2011, A5E01071724-03
63
Assigning parameters using the parameter assignment interface
For initial commissioning of the module, assign parameters for the module using the
parameter assignment interface. Observe the following order:
Step Description ✓
1 Select the tier in the rack containing the FM 352 module. ❑
2 Next, double-click the entry to open the parameter assignment interface for
FM 352.
❑
3 Select File > Properties to edit the following settings:
General
You can edit the name and enter a comment.
Addresses
You can edit the start address and assign the address area to a process
image partition.
Note the module address displayed.
Basic parameters
You can set the interrupt type and the reaction to a CPU STOP.
❑
4 In the block diagram shown, you can select the Axis, Encoders, Cams,
Tracks and Interrupt Enable dialog boxes, and set the relevant parameters.
❑
5 Select File > Save to save the parameter assignment. ❑
6 Close the parameter assignment interface by selecting File > Exit. ❑
7 Backup the hardware configuration in HW Config by selecting Station >
Save and Compile.
❑
8 Go online and download the hardware configuration to the CPU: The CPU
transfers those data to the FM 352 at each STOP to RUN transition.
❑
9 Select Test > Commissioning. ❑
Test and Commissioning
You can now test your entries and changes.
Step Description ✓
1 To test your commissioning data, select the Test > Commission, Test >
Service and Test > Error Evaluation screen forms.
❑
2 You can modify faulty machine data in the Test > Commissioning screen
form. These changes remain valid until the next CPU STOP to RUN
transition.
❑
3 You can save the corrected machine data to the CPU by repeating steps 7
to 9 of the sequence.
❑
Note
If you are using the FM 352 on PROFINET or PROFIBUS DP, the CPU must be in RUN
mode for testing and commissioning. Otherwise, you cannot control the FM 352.