Digital electronic modules
3.17 2DO 24 VDC/2 A High Feature digital electronic module (6ES7132-4BB31-0AB0)
ET 200S
3-72 Manual, Edition 10/2005, A5E00514527-01
Lamp load max. 5 W
Connecting two outputs in parallel
• For redundant triggering of a load
Yes (per module)
• To increase performance
no
Control of a digital input Yes
Switch rate
• For resistive load
100 Hz
• On inductive load
2 Hz (0.5 H)
• For lamp load
10 Hz
Limitation (internal) of the voltage induced on
circuit interruption
Typically L+ (-55 to -60 V)
Reverse-voltage proof Yes, if using the same load voltage as at the
power module
Short-circuit protection of the output Yes
2
• Threshold on
Typically 4 A
1
Polarity reversal can lead to the digital outputs being connected through.
2
Per channel