Digital electronic modules
3.18 2DO 24 VAC to 230 VAC digital electronic module (6ES7132-4FB01-0AB0)
ET 200S
3-76 Manual, Edition 10/2005, A5E00514527-01
Motor starter size
• Up to 40° C
Max. size in accordance with NEMA: 5
• Up to 60° C
Max. size in accordance with NEMA: 4
Lamp load max. 100 W
Connecting two outputs in parallel
• For redundant triggering of a load
Yes (per module)
• To increase performance
no
Control of a digital input supported
Switch rate
• For resistive load
max. 10 Hz
• On inductive load
max. 0.5 Hz
• For lamp load
max. 1 Hz
Short-circuit protection of the output Yes, by means of fuse in the power module
1
Total current of the outputs (per module): see the diagram below
Total current of the outputs
$ $ $
r&
r&
r&
7RWDOFXUUHQWSHUPRGXOH
7HPSHUDWXUH
Figure 3-20 Total current of the outputs for 2DO 24 VAC to 230 VAC