Analog electronic modules
4.10 4AI I 2WIRE Standard analog electronic module (6ES7134-4GD00-0AB0)
ET 200S
Manual, Edition 10/2005, A5E00514527-01
4-55
4AI I 2WIRE Standard Technical Specifications (6ES7134-4GD00-0AB0)
Dimensions and Weight
Dimensions W × H × D (mm)
(the total dimensions depend on the selected
terminal module)
15 × 81 × 52
Weight Approx. 40 g
Data for specific modules
Supports isochronous operation no
Number of inputs 4
Cable length
Shielded
max. 200 m
Parameter length 7 bytes
Voltages, currents, potentials
Rated load voltage L+ (from the power module) 24 VDC
Reverse polarity protection
Yes
Power supply of the transmitters Yes
Short-circuit protection
Yes (approx. 200 mA for module)
Galvanic isolation
Between the channels and backplane bus
Yes
Between the channels and load voltage L+
no
Between the channels
no
Insulation tested 500 VDC
Current consumption of the module
From the load voltage L+ (with sensor
supply)
max. 125 mA
Power dissipation of the module Typically 0.6 W
Status, interrupts, diagnostics
Diagnostics function
Group error
Red "SF" LED
Diagnostic functions readable
Yes
Analog value generation
Measuring principle Integrative
Integration and cycle time/resolution per
channel:
Integration time can be assigned parameters
Yes
Interference frequency suppression in Hz
60 50
Integration time in milliseconds
16.7 20
Cycle time per module in ms
33 40
Resolution (including overrange)
4 mA to 20 mA/13 bits