Analog electronic modules
4.13 2AI I 2/4WIRE High Feature analog electronic module (6ES7134-4MB00-0AB0)
ET 200S
4-68 Manual, Edition 10/2005, A5E00514527-01
Suppression of interference, limits of error
Interference voltage suppression for
f = n x (f1 ± 0.5 %), (f1 = interference
frequency)
Common-mode interference (U
SS
)
Series-mode interference
(peak interference value < rated value of
input range)
min. 100 dB
min. 90 dB
Crosstalk between the inputs min. -100 dB
Operational limit
1
(over the entire temperature range, with
reference to the input range)
± 0.1 %
Basic error limit
1
operational limit at 25 °C with reference to
input range
± 0.05 %
Temperature error (with reference to the
input range)
± 0.003 %/K
Linearity error (with reference to the input
range)
± 0.03 %
Repeatability
(in steady state at 25° C with reference to
input range)
± 0.01 %
Data for selecting a sensor
Input range (rated value)/input resistance
Current
± 20 mA/50 Ω
4 mA to 20 mA/50 Ω
Permitted input current (destruction limit) 40 mA (on a single channel)
Load of the two-wire measuring transducer max. 750 Ω
Smoothing of the measured values Yes, can be assigned parameters in 4 steps by
means of digital filtering
Step
None
Weak
Medium
Strong
Time constant
1 x cycle time
4 x cycle time
32 x cycle time
64 x cycle time
1
Run-time calibration can be enabled during module parameter assignment to periodically adjust for
the offset voltage drift of the A/D converter. During the calibration interval, the updating of new data is
delayed by 200 ms. The accuracy limits of the module will be met without run-time calibration.