Analog electronic modules
4.17 2AI TC Standard analog electronic module (6ES7134-4JB00-0AB0)
ET 200S
Manual, Edition 10/2005, A5E00514527-01
4-89
Data for selecting a sensor
Input range (rated value)/input resistance
Voltage
± 80 mV/min. 1 MΩ
Thermocouple
Type E, N, J, K, L, S, R, B, T/min. 1 MΩ
Permitted input voltage (destruction limit) ± 10 V, continuous
Connection of the sensors
For measuring voltage
supported
Characteristic curve linearization Yes, can be assigned parameters for type E, N, J, K, L,
S, R, B, T as per IEC 584
Temperature compensation
Internal temperature compensation
not supported
External temperature compensation by
looping a compensating box into the
measuring circuit
Possible, one external compensating box per channel
External compensation by means of
temperature value obtained at an
analog module of the same ET 200S
station
Yes
Smoothing of the measured values Yes, can be assigned parameters in 4 steps by means of
digital filtering
Step
None
Weak
Medium
Strong
Time constant
1 x cycle time
4 x cycle time
32 x cycle time
64 x cycle time
1
for Type N: from -150 °C, type B: from 200 °C, type T: from -230 °C
Compensation of thermocouples with a compensating box
As well as the error limits of the 2AI TC Standard electronic module (see Table "Technical
specifications 2AI TC Standard (6ES7134-4JB00-0AB0)" in this chapter) you must also take
the accuracy of the compensating box into account.