Analog electronic modules
4.22 2AO I High Feature analog electronic module (6ES7135-4MB02-0AB0)
ET 200S
Manual, Edition 10/2005, A5E00514527-01
4-109
Status, interrupts, diagnostics
Diagnostics function
Group error display
Red "SF" LED
Diagnostic information readable
Yes
Substitute values can be applied Yes, parameterizable
Analog value generation
Resolution (including sign) ± 20 mA/16 bits
4 to 20 mA/15 bits
Conversion time (per channel) max. 1.0 ms
Settling time
For resistive load
0.25 ms
For capacitive load
1.0 ms
For inductive load
0.5 ms
Suppression of interference, limits of error
Crosstalk between the outputs > 60 dB
Operational limit (in the entire temperature
range, with reference to the output range)
±0.07 % (at 250 O load impedance)
±0.3 % (for all other load impedances)
Basic error limit (operational limit at 25 °C with
reference to output range)
±0.03 % (at 250 O load impedance)
±0.26 % (for all other load impedances)
Temperature error (with reference to the
output range)
± 0.001 %/K
Linearity error (with reference to the output
range)
± 0.02 %
Repeatability
(in steady state at 25 °C with reference to
output range)
± 0.01 %
Output ripple (with reference to output range,
bandwidth 0 to 50 kHz)
± 0.02 %
Data for selecting an actuator
Output range (rated value) ± 20 mA
4 to 20 mA
Load impedance (in the rated range of the
output)
For current outputs
For inductive load
max. 500 Ω
1 mH
Current output
Open circuit voltage
18 V
Destruction limit against voltages/currents
applied from outside
Voltage at the outputs to M
ANA
15 V continuous; 75 V for max. 1 ms
(sampling ratio 1:20)
Current
max. 50 mA DC
Connection of actuators
Current output
Two-wire connection
supported

Table of Contents

Related product manuals