EasyManua.ls Logo

Siemens Simatic S7-300 - Page 115

Siemens Simatic S7-300
594 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Digital modules
3.22 Digital output module SM 322; DO 16 x AC 120/230 V/1 A; (6ES7322-1FH00-0AA0)
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
3-67
Technical data of SM 322; DO 16 x AC 120/230 V/1 A
Technical data
Dimensions and weight
Dimensions W x H x D 40 x 125 x 117
Weight approx. 275 g
Module-specific data
Isochronous mode supported No
Number of outputs 16
Cable length
unshielded
shielded
max. 600 m
max. 1000 m
Voltages, currents, electrical potentials
Load voltage L1
All load voltages must be connected to the same phase
120/230 VAC
Cumulative current of outputs (per group)
horizontal mounting position
up to 40 °C
up to 60 °C
max. 4 A
max. 2 A
vertical mounting position
up to 40 °C
max. 2 A
Electrical isolation
between channels and the backplane bus
Yes
Between channels
in groups of
Yes
8
Permissible potential difference
between M
internal
and outputs
230 VAC
between outputs of different groups
500 VAC
Isolation test voltage 4000 VDC
Current consumption
from the backplane bus
from load voltage L+ (no-load)
max. 200 mA
max. 2 mA
Power loss of the module typ. 8.6 W
Status, interrupts, diagnostics
Status display green LED per channel
Interrupts
Diagnostic interrupt
No
Diagnostics functions
Group error display
red LED (SF)
(fuse or no L1/N)
Actuator selection data
Output voltage
with "1" signal
At maximum current
At minimum current
min. L 1 (- 1.5 V)
min. L 1 (-8.5 V)