Analog modules
6.11 Analog output module SM 332; AO 8 x 12 Bit; (6ES7332-5HF00-0AB0)
S7-300 Automation System Module data
6-100 Manual, 08/2006, A5E00105505-04
Programming restrictions when operating SM 331; AI 8 x TC with PROFIBUS masters which only
support DPV0.
When operating the SM 331; AI 8 xTC analog input module on an ET 200M PROFIBUS
slave system and the PROFIBUS master is not an S7 master, certain parameters are not
permitted. Non-S7 masters do not support hardware interrupts. All parameters associated
with those functions are thus disabled. This includes hardware interrupt enable, hardware
restrictions and end of cycle interrupt enable. All other parameters are permitted.
Operation of the module on the ET 200M Distributed IO Device
Operation of SM 331; AI 8 x TC on ET 200M requires one of the following IM 153 x:
IM 153-1; as of 6ES7153-1AA03-0XB0, E 01
IM 153-2; as of 6ES7153-2AA02-0XB0, E 05
IM 153-2; as of 6ES7153-2AB01-0XB0, E 04
6.11 6.11 Analog output module SM 332; AO 8 x 12 Bit; (6ES7332-5HF00-
0AB0)
Order number
6ES7332-5HF00-0AB0
Properties
8 outputs in one group
The output can be selected by individual channel
Voltage output
Current output
Resolution 12 bits
Programmable diagnostics and diagnostic interrupt
Programmable diagnostic alarm
electrically isolated to the backplane bus interface and load voltage
Diagnostics
For information on diagnostics message consolidated at the "group diagnostics" parameter,
refer to the table
Diagnostics messages of analog output modules
.