Representation of the analog values of analog modules
5.1 Representation of the analog values of analog input channels
S7-300 Automation System Module data
5-8 Manual, 08/2006, A5E00105505-04
Presentation of analog values for resistance thermometers Pt x00 and Pt x0 GOST (0.003850)
standard
Table 5-13 Presentation of analog values for resistance thermometers Pt 100, 200, 500,1000 und Pt 10, 50, 100, 500
GOST (0.003850) Klima
Units Units Pt x00
Klima/
GOST in °C
(1 digit =
0.01°C)
dec hexa-
decimal
Pt x00
Klima/
GOST in °F
(1 digit =
0.01 °F)
dec hexa-
decimal
Range
> 155.00 32767 7FFF
H
> 311.00 32767 7FFF
H
Overflow
155.00
:
130.01
15500
:
13001
3C8C
H
:
32C9
H
311.00
:
266.01
31100
:
26601
797C
H
:
67E9
H
Overshoot range
130.00
:
-120.00
13000
:
-12000
32C8
H
:
D120
H
266.00
:
-184.00
26600
:
-18400
67E8
H
:
B820
H
Nominal range
-120.01
:
-145.00
-12001
:
-14500
D11F
H
:
C75C
H
-184.01
:
-229.00
-18401
:
-22900
B81F
H
:
A68C
H
Undershoot range
< - 145.00 -32768 8000
H
< - 229.00 -32768 8000
H
Underflow
Representation of the analog values of Ni x00 Standard resistance thermometers
Table 5-14 Representation of the analog values of Ni100, 120, 200, 500, 1000 and
LG-Ni 1000 resistance thermometers
Units Units Units Ni x00
Standard in
°C (1 digit =
0.1°C)
dec hexa-
decimal
Ni x00
Standard in
°F (1 digit =
0.1 °F)
dec hexa-
decimal
Ni x00
standard in
K (1 digit =
0.1 K)
dec hexa-
decimal
Range
> 295.0 32767 7FFF
H
> 563.0 32767 7FFF
H
> 568.2 32767 7FFF
H
Overflow
295.0
:
250.1
2950
:
2501
B86
H
:
9C5
H
563.0
:
482.1
5630
:
4821
15FE
H
:
12D5
H
568.2
:
523.3
5682
:
5233
1632
H
:
1471
H
Overshoot
range
250.0
:
-60.0
2500
:
-600
9C4
H
:
FDA8
H
482.0
:
-76.0
4820
:
-760
12D4
H
:
FD08
H
523.2
:
213.2
5232
:
2132
1470
H
:
854
H
Nominal
range
-60.1
:
-105.0
-601
:
-1050
FDA7
H
:
FBE6
H
-76.1
:
-157.0
-761
:
-1570
FD07
H
:
F9DE
H
213.1
:
168.2
2131
:
1682
853
H
:
692
H
Underflow
range
< -105.0 -32768 8000
H
< -157.0 -32768 8000
H
< 168.2 32768 8000
H
Underflow