Analog modules
6.3 Analog input module SM 331; AI 8 x 16 Bit; (6ES7331-7NF00-0AB0)
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
6-13
6.3.1 Measuring methods and ranges
Introduction
Use the "measuring range" parameter in
STEP 7
to set the measuring method and
measuring ranges.
The "voltage" measuring method and "± 10V" measuring range are set by default at the
module. You can use those default settings without having to program the SM 331; AI 8 x 16
Bit in
STEP 7
.
Measuring methods and ranges
Table 6-5 Measuring methods and ranges
Selected measuring method Measuring range
V voltage: ±5 V
1 V to 5 V
±10 V
Current 0 mA to 20 mA
±20 mA
4 mA to 20 mA
6.3.2 Adjustable parameters
Introduction
For information on programming analog modules, refer to the chapter
Programming analog
modules
.
Parameters
Table 6-6 Overview of parameters of SM 331; AI 8 x 16 Bit
Parameters Range of values Default Parameter
type
Scope
Enable
Diagnostic interrupt
Hardware interrupt when
limit exceeded
Yes/no
Yes/no
No
No
Dynamic
Module
Hardware interrupt trigger
High limit
Low limit
May be restricted by the measuring range.
from 32511 to - 32512
from - 32512 to 32511
-
Dynamic
Channel
Diagnostics
Group diagnostics
with wirebreak monitoring
Yes/no
Yes/no
No
No
static
Channel
group