EasyManua.ls Logo

Siemens Simatic S7-300 - Page 246

Siemens Simatic S7-300
594 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog modules
6.3 Analog input module SM 331; AI 8 x 16 Bit; (6ES7331-7NF00-0AB0)
S7-300 Automation System Module data
6-12 Manual, 08/2006, A5E00105505-04
Technical data
Basic error limit (operational error limit at 25 °C relative to input range)
Voltage input
Current input
±0,05%
±0,05%
Temperature error (relative to input range) ±0.005%/K
Linearity error (relative to input range) ±0,03%
Repetition accuracy (in transient state at 25 °C, relative to input
range)
±0,025%
Status, interrupts, diagnostics
Interrupts
Hardware interrupt when limit has been exceeded
Diagnostic interrupt
programmable
Channels 0 and 2
programmable
Diagnostics functions
Group error display
Reading diagnostics information
programmable
red LED (SF)
supported
Transducer selection data
Input ranges (rated values) / input impedance
Voltage
± 5 V
1 to 5 V
± 10 V
/ 2 MΩ
/ 2 MΩ
/ 2 MΩ
Current
0 mA to 20 mA
± 20 mA
4 mA to 20 mA
/ 250 Ω
/ 250 Ω
/ 250 Ω
Permissible voltage at voltage input (destruction limit) max. 50 V, continuous
Permissible current at current input (destruction limit) max. 32 mA
Wiring signal transducers with 40-pin front connector
for voltage measurement
for current measurement
as 2-wire transducer
as 4-wire transducer
Load of the 2-wire transducer
supported
possible, with separate transducer supply
supported
max. 820 Ω