Analog modules
6.16 Analog IO module SM 334; AI 4/AO 2 x 12 bit; (6ES7334-0KE00-0AB0)
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
6-145
Measuring ranges
Program the measuring ranges in
STEP 7
.
Table 6-41 Measuring methods and ranges
Selected measuring method Measuring range
V: Voltage 0 V to 10 V
R-4L: resistance (4-wire connection) 10 kΩ
RTD-4L: Thermoelectric resistance
(linear, 4-wire connection)
(temperature measurement)
Pt 100 Klima
Output ranges of SM 334; AI 4/ AO 2 x 12 bit
The "voltage" output type and "0 V to 10 V" output range are set by default at the module.
You can always use this combination of the output type and range without having to program
the SM 334; AO 4 x 2 Bit in
STEP 7
.
Table 6-42 Output ranges
Selected type of output Output range
Voltage 0 V to 10 V
See also
Representation of the analog values of analog output channels (Page 5-18)
6.16.3 Additional information to SM 334; AI 4/ AO 2 x 12 bit
Unused channels
Set the "disabled" argument at the "measuring method" parameter for unused input
channels. This reduces the module's cycle time.
Always short-circuit unused input channels, and connect these to M
ANA
. This optimizes
interference immunity of the analog input module.
To take the unused output channels of SM 334; AI 4/AO 2 x 12 Bit off power, always set
"disabled" argument at the "output type" parameter, and leave the connection open.