Representation of the analog values of analog modules
5.1 Representation of the analog values of analog input channels
S7-300 Automation System Module data
5-12 Manual, 08/2006, A5E00105505-04
Representation of the analog values of Cu 10, 50, 100, 500 GOST Standard (0.00428) resistance
thermometers
Table 5-21 Representation of the analog values of Cu 10, 50, 100, 500 GOST Standard resistance thermometers
Units Units
Cu 10
climate in
°C (1 digit =
0.01°C)
dec hexa-
decimal
Cu 10
climate in
°F (1 digit =
0.01 °F)
dec hexa-
decimal
Range
> 180.00 32767 7FFF
H
> 325.11 32767 7FFF
H
Overflow
180.00
:
150.01
18000
:
15001
4650
H
:
3A99
H
327.66
:
280.01
32766
:
28001
7FFE
H
:
6D61A
H
Overshoot range
150.00
:
-50.00
15000
:
-5000
3A98
H
:
EC78
H
280.00
:
-58.00
28000
:
-5800
6D60
H
:
E958
H
Nominal range
-50.01
:
-60.00
-5001
:
-6000
EC77
H
:
E890
H
-58.01
:
-76.00
-5801
:
-7600
E957
H
:
E250
H
Undershoot range
< - 60.00 -32768 8000
H
< - 76.00 -32768 8000
H
Underflow
Representation of the analog values of thermocouples type B
Table 5-22 Representation of the analog values of thermocouples type B
Units Units Units
Type B in
°C
dec hexa-
decimal
Type B in
°F
dec hexa-
decimal
Type B in K
dec hexa-
decimal
Range
> 2070.0 32767 7FFF
H
> 3276.6 32767 7FFF
H
> 2343.2 32767 7FFF
H
Overflow
2070.0
:
1821.0
20700
:
18210
50DC
H
:
4722
H
3276.6
:
2786.6
32766
:
27866
7FFE
H
:
6CDA
H
2343.2
:
2094.2
23432
:
20942
5B88
H
:
51CE
H
Overshoot
range
1820.0
:
0.0
18200
:
0
4718
H
:
0000
H
2786.5
:
32.0
27865
:
320
6CD9
H
:
0140
H
2093.2
:
273.2
20932
:
2732
51C4
H
:
0AAC
H
Nominal
range
:
-120.0
:
-1200
:
FB50
H
:
-184.0
:
-1840
:
F8D0
H
:
153.2
:
1532
:
05FC
H
Underflow
range
< -120.0 -32768 8000
H
< -184.0 -32768 8000
H
< 153.2 32768 8000
H
Underflow