EasyManua.ls Logo

Siemens Simatic S7-300 - Parameters of Analog Output Module SM 332; AO 8 X 12 Bit

Siemens Simatic S7-300
594 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter sets of signal modules
A.10 Parameters of analog output module SM 332; AO 8 x 12 Bit
S7-300 Automation System Module data
A-38 Manual, 08/2006, A5E00105505-04
Output types and output ranges
The table below lists all output types/ranges of the analog output modules, including their
codes. Enter these codes at bytes 2 to 5 in data record 1 (refer to the previous figure.)
Table A-29 Output range codes of analog output modules
Output type Code Output range Code
disabled 2#0000 disabled 2#0000
Voltage 2#0001 1 V to 5 V
0 V to 10 V
± 10 V
2#0111
2#1000
2#1001
Current 2#0010 0 mA to 20 mA
4 mA to 20 mA
± 20 mA
2#0010
2#0011
2#0100
See also
Analog modules (Page 6-1)
A.10 A. 10 Parameters of analog output module SM 332; AO 8 x 12 Bit
Parameters
The table below shows all parameters you can set at analog output module SM 332; AO 8 x
12 Bit. The comparison shows:
which parameters you can edit in
STEP 7
, and
which parameters you can change using SFC 55 "WR_PARM".
Parameters set in
STEP 7
can also be transferred to the module using SFC 56 and SFC 57.
Table A-30 Parameters of SM 332; AO 8 x 12 Bit
Programmable, using ...
Parameters Data record
number
... SFC 55 ... PG
Diagnostics: Group diagnostics 0 No Yes
Diagnostics interrupt enable Yes Yes
Reaction to CPU STOP Yes Yes
Output type Yes Yes
Output range
1
Yes Yes

Table of Contents

Other manuals for Siemens Simatic S7-300

Related product manuals