Parameter sets of signal modules
A.10 Parameters of analog output module SM 332; AO 8 x 12 Bit
S7-300 Automation System Module data
A-38 Manual, 08/2006, A5E00105505-04
Output types and output ranges
The table below lists all output types/ranges of the analog output modules, including their
codes. Enter these codes at bytes 2 to 5 in data record 1 (refer to the previous figure.)
Table A-29 Output range codes of analog output modules
Output type Code Output range Code
disabled 2#0000 disabled 2#0000
Voltage 2#0001 1 V to 5 V
0 V to 10 V
± 10 V
2#0111
2#1000
2#1001
Current 2#0010 0 mA to 20 mA
4 mA to 20 mA
± 20 mA
2#0010
2#0011
2#0100
See also
Analog modules (Page 6-1)
A.10 A. 10 Parameters of analog output module SM 332; AO 8 x 12 Bit
Parameters
The table below shows all parameters you can set at analog output module SM 332; AO 8 x
12 Bit. The comparison shows:
● which parameters you can edit in
STEP 7
, and
● which parameters you can change using SFC 55 "WR_PARM".
Parameters set in
STEP 7
can also be transferred to the module using SFC 56 and SFC 57.
Table A-30 Parameters of SM 332; AO 8 x 12 Bit
Programmable, using ...
Parameters Data record
number
... SFC 55 ... PG
Diagnostics: Group diagnostics 0 No Yes
Diagnostics interrupt enable Yes Yes
Reaction to CPU STOP Yes Yes
Output type Yes Yes
Output range
1
Yes Yes