EasyManua.ls Logo

Siemens Simatic S7-300

Siemens Simatic S7-300
594 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog modules
6.6 Analog input module SM 331; AI 8 x 13 Bit;(6ES7331-1KF01-0AB0)
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
6-47
6.6.2 Adjustable parameters
Introduction
For general information on programming analog modules, refer to the chapter
Programming
analog modules
.
Parameters
Table 6-17 Parameters of SM 331; AI 8 x 13 Bit
Parameters Range of values Default Parameter
type
Scope
Measurement
Measuring method
disabled
V voltage
I current
R resistance
RTD thermoelectric resistance
V
Voltage
± 50 mV; ± 500 mV; ±1 V;
1 V to 5 V
± 5 V; 0 to 10 V; ± 10 V
± 10 V
Current
0 mA to 20 mA; 4 mA to 20 mA; ± 20 mA
± 20 mA
Resistance
0 Ω to 600 Ω; 0 kΩ to 6 kΩ
600 Ω
Measuring range
Thermoelectric resistance (linear)
Pt 100 Klima / Standard
Ni 100 Klima / Standard
Ni 1000 Klima / Standard
LG-Ni 1000 Klima / Standard
Pt 100
standard
Temperature coefficient
Pt 100
0.003850 Ω/Ω/ °C (IST-90)
Ni 100 / Ni 1000
0,006180 Ω/Ω/ °C
LG-Ni 1000
0.005000 Ω/Ω/ °C
0,003850
Channel
Noise suppression
50 Hz; 60 Hz 50 Hz
Temperature unit
Degrees Centigrade, degrees Fahrenheit,
Kelvin*
Degrees
Centigrade
Dynamic
Module
* only Pt 100 Standard, Ni 100 Standard, Ni 1000 Standard, LG-Ni 1000 Standard
See also
Programming analog modules (Page 5-31)

Table of Contents