Digital modules
3.27 Digital output module SM 322; DO 8 x AC 120/230 V/2 A ISOL (6ES7322-5FF00-0AB0)
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
3-91
Technical data
Lamp load max. 50 W
Wiring two outputs in parallel
for redundant load control
supported
for performance increase
not supported
Control of a digital input supported
Switching frequency
with resistive load
max. 10 Hz
with inductive load to IEC 947-5-1, AC 15
max. 0.5 Hz
with lamp load
max. 1 Hz
Short circuit-proof output Yes, 3.15 A / 250 V fuse, fast-blow
Wiring the actuators with 20-pin front connector
Note
The outputs must be protected by a high-speed, fast-blow 3.15 A 250 VAC fuse. When
installed in a hazardous area to National Electric Code, the area must be designated safe
before you replace the fuse. Always use a suitable tool.
3.27.1 Parameters of SM 322; DO 8 x AC 120/230 V/2 A ISOL
Parameters of SM 322; DO 8 x AC 120/230 V/2 A ISOL
The table below lists the configurable parameters of SM 322; DO 8 x AC120/230 V/2 A
ISOL, including defaults.
The defaults apply if you have not set any parameters in
STEP 7
.
Table 3-22 Parameters of SM 322; DO 8 x AC 120/230 V/2 A ISOL
Parameters Range of values Defaults Parameter type Scope
Enable
Diagnostic interrupts
Yes/no
No
Dynamic
Module
Reaction to CPU STOP Set substitution value
Hold last value
SSV Dynamic Channel
Set substitution value "1" Yes/no No Dynamic Channel
Programming
For detailed information on parameters of the digital output module, refer to the appendix.
See also
Parameters of digital output modules (Page A-4)