EasyManua.ls Logo

Siemens Simatic S7-300

Siemens Simatic S7-300
594 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Power supply modules
2.1 Power Supply Module PS 305; 2 A; (6AG1305-1BA80-0AA0)
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
2-3
Line protection
The mains supply of the PS 305 power supply module (2 A) should be protected with a
miniature circuit-breaker (for example Siemens 5SN1 series) of the following rating:
Rated current at 110 VDC: 10 A
Tripping characteristics (type): C.
Reaction to atypical operating conditions
Table 2-1 Reaction of the PS 305;(2 A) power supply module to atypical operating conditions
If ... ... then ... 24 VDC LED
... the output circuit is overloaded:
I > 3.9 A (dynamic)
3 A < I ≤ 3.9 A (static)
Voltage dip, automatic voltage recovery
Voltage drop, reduction of service life
flashes
... short-circuit at the output Output voltage 0 V; automatic voltage recovery
after short-circuit is eliminated
off
overvoltage on primary side risk of destruction -
undervoltage on primary side Automatic shut-down; automatic voltage
recovery
off
Technical data of PS 305; 2 A (6ES7305-1BA80-0AA0)
Technical data
Dimensions and weight
Dimensions W x H x D (mm) 80 x 125 x 120
Weight approx. 740 g
Input parameters
Input voltage
Rated value
Voltage range
24/48/72/96/110 VDC
16.8 VDC to 138 VDC
Rated input current
at 24 V
at 48 V
at 72 V
at 96 V
at 110 V
2.7 A
1.3 A
0.9 A
0.65 A
0.6 A
Inrush current (at 25 °C) 20 A
I
2
t (at inrush current) 5 A
2
s
Output parameters
Output voltage
Rated value
Permissible range
24 VDC
24 V ± 3 %, open circuit-proof
Rampup time
max. 3 s

Table of Contents