Analog modules
6.11 Analog output module SM 332; AO 8 x 12 Bit; (6ES7332-5HF00-0AB0)
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
6-105
6.11.1 Output ranges SM 332; AO 8 x 12 Bit
Introduction
You can configure the outputs for operation as voltage or current outputs, or disable them.
You configure the outputs at the "output type" parameter in
STEP 7
.
The output type "Voltage" and output range "± 10 V" are set by default at the module. You
can always use this combination of output type and range without having to program the
SM 332; AO 8 x 12 Bit in
STEP 7
.
Table 6-32 Output ranges
Selected type of output Output range
Voltage 1 V to 5 V
0 V to 10 V
± 10 V
Current 0 mA to 20 mA
4 mA to 20 mA
± 20 mA
See also
Representation of the analog values of analog output channels (Page 5-18)
6.11.2 Adjustable parameters
Introduction
For general information on programming analog modules, refer to the chapter
Programming
analog modules
.
The table below provides an overview of configurable parameters, including defaults:
Table 6-33 Summary of parameters SM 332; AO 8 x 12 Bit
Parameters Range of values Default Parameter
type
Scope
Enable
• Diagnostic interrupt
Yes/no
No
Dynamic
Module
Diagnostics
• Group diagnostics
Yes/no
No
static
Channel
Output
• Output type
• Output range
disabled
Voltage
Current
See table of
output ranges
V
± 10 V
Dynamic Channel
Reaction to CPU STOP ASS
HLV
SSV
Outputs zero
current/voltage
Hold last value
Set substitution
value
ASS Dynamic Channel