EasyManua.ls Logo

Siemens Simatic S7-300 - Page 124

Siemens Simatic S7-300
594 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Digital modules
3.24 Digital output module SM 322; DO 8 x DC 24 V/ 0.5 A; with diagnostics interrupt; (6ES7322-8BF00-0AB0)
S7-300 Automation System Module data
3-76 Manual, 08/2006, A5E00105505-04
Technical data
Diagnostics functions
Group error display
Channel error display (F)
Reading diagnostics data
programmable
red LED (SF)
red LED (F) per channel
supported
Actuator selection data
Output voltage
with "1" signal
without series diode
with series diode
min. L + (- 0.8 V)
min. L+ (-1.6 V)
Output current
with "1" signal
Rated value
Permissible range
0.5 A
10 mA to 0.6 A
1)
with "0" signal (residual current)
max. 0.5 mA
Output delay (resistive load)
at "0" to "1" transitions
at "1" to "0" transitions
max. 180 μs
max. 245 μs
Load resistance range 48 Ω to 3 kΩ
Lamp load max. 5 W
Wiring two outputs in parallel
for redundant load control
Only outputs with series diode and common
reference potential
for performance increase
not supported
Control of a digital input supported
1 binary input to IEC 61131, Type 2;
Type 1, with disabled wire-break monitoring
Switching frequency
with resistive load
with inductive load to IEC 947-5-1, DC 13
with lamp load
max. 100 Hz
max. 2 Hz
max. 10 Hz
Internal limiting of the inductive shutdown voltage to typ. L + (-45 V)
Short circuit-proof output Yes, electronic
Threshold
typ. 0.75 A to 1.5 A
Wiring the actuators with 20-pin front connector
1) 5 mA to 0.6 A, with disabled wire-break monitoring

Table of Contents

Other manuals for Siemens Simatic S7-300

Related product manuals