Digital modules
3.29 Relay output module SM 322; DO 8 x Rel. AC 230 V; (6ES7322-1HF01-0AA0)
S7-300 Automation System Module data
3-100 Manual, 08/2006, A5E00105505-04
Technical data
Voltage
Current Number of switching cycles
(typ.)
24 VDC
60 VDC
120 VDC
48 VAC
60 VAC
120 VAC
230 VAC
2.0 A
1.0 A
0.5 A
0.5 A
0.2 A
2.0 A
2.0 A
2.0 A
1.0 A
0.5 A
2.0 A
1.0 A
0.5 A
0.7 million
1.6 million
4 million
1.6 million
1.6 million
1.6 million
1.2 million
0.5 million
2)
0.7 million
2)
1.5 Mio
2)
0.5 million
2)
0.7 million
2)
1.5 million
• with inductive load to IEC 947-5-1 DC13/AC15
Voltage Current Number of switching cycles
(typ.)
24 VDC
60 VDC
120 VDC
48 VAC
60 VAC
120 VAC
230 VAC
2.0 A
1.0 A
0.5 A
0.5 A
0.2 A
1.5 A
1.5 A
2.0 A
1.0 A
0.7 A
0.5 A
2.0 A
1.0 A
0.5 A
0.3 million
0.5 million
1.0 million
0.5 million
0.3 million
2)
1 million
1 million
0.2 million
0.7 million
1 million
2.0 million
0.3 million
2)
0.7 million
2)
2.0 Mio
2)
Contact protection (internal) Varistor SIOV-CU4032 K275 G
An external protective circuit will increase the service life of contacts.
Actuator selection data [continued]
Lamp load
1)
max. 50 W
Power Number of switching cycles
(typ.)
Lamp load (230 VAC)
2)
700 W
1500 W
25000
10000
Energy-saving lamps/fluorescent lamps with electronic ballast
2)
10 58 W 25000
Fluorescent lamps, conventionally compensated
2)
1 x 58 W 25000
Fluorescent lamps, non-compensated
2)
10 x 58 W 25000