EasyManua.ls Logo

Siemens Simatic S7-300 - Page 24

Siemens Simatic S7-300
594 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
General technical data
1.2 Electromagnetic Compatibility
S7-300 Automation System Module data
1-6 Manual, 08/2006, A5E00105505-04
Sinusoidal disturbance
The table below shows the EMC compatibility of S7-300 modules in areas subject to
sinusoidal disturbance.
Sinusoidal disturbance Test values corresponds with
degree of severity
RF radiation
(electromagnetic fields)
to IEC 61000-4-3
10 V/m, with 80% amplitude modulation of
1 kHz in the 80 MHz to 1000 MHz range
10 V/m, with 50% pulse modulation at
900 MHz
3
RF conductance on cables
and cable shielding
to IEC 61000-4-6
Test voltage 10 V, with 80% amplitude
modulation of 1 kHz in the 9 MHz to 80 MHz
range
3
Emission of radio interference
Electromagnetic interference to EN 55011: Limit Class A, Group 1 (measured at a distance
of 10 m.)
Frequency Noise emission
30 MHz to 230 MHz < 40 dB (µV/m)Q
230 MHz to 1000 MHz < 47 dB (µV/m)Q
Noise emission via AC mains to EN 55011: Limit value class A, Group 1.
Frequency Noise emission
0.15 MHz to 0.5 MHz < 79 dB (µV/m)Q
< 66 dB (µV/m)M
0.5 MHz to 5 MHz < 73 dB (µV/m)Q
< 60 dB (µV/m)M
5 MHz to 30 MHz < 73 dB (µV/m)Q
< 60 dB (µV/m)M