EasyManua.ls Logo

Siemens Simatic S7-300 - Page 290

Siemens Simatic S7-300
594 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog modules
6.7 Analog input module SM 331; AI 8 x 12 Bit;(6ES7331-7KF02-0AB0)
S7-300 Automation System Module data
6-56 Manual, 08/2006, A5E00105505-04
Technical data
Transducer selection data
Input ranges (rated values) / input impedance
Voltage
± 80 mV
± 250 mV
± 500 mV
± 1000 mV
± 2.5 V
± 5 V
1 V to 5 V
± 10 V
10 MΩ
10 MΩ
10 MΩ
10 MΩ
/100 kΩ
/100 kΩ
/100 kΩ
/100 kΩ
Current
± 3.2 mA
± 10 mA
± 20 mA
0 mA to 20 mA
4 mA to 20 mA
25 Ω
25 Ω
25 Ω
25 Ω
25 Ω
Resistance
150 Ω
300 Ω
600 Ω
/10 MΩ
/10 MΩ
/10 MΩ
Thermocouples
Types E, N, J, K, L /10 MΩ
Resistance thermometers
Pt 100, Ni 100 /10 MΩ
Permissible voltage at voltage input (destruction limit) max. 20 V, continuous
75 V for the duration of max. 1 s (duty factor 1:20)
Permissible current at current input (destruction limit) max. 40 mA
Wiring signal transducers with 20-pin front connector
for voltage measurement
supported
for current measurement
as 2-wire transducer
as 4-wire transducer
supported
supported
for resistance measurement
with 2-wire connection
possible, no compensation for line resistor
with 3-wire connection supported
with 4-wire connection supported
Load of the 2-wire transducer
max. 820 Ω
Characteristic linearization
for thermocouples
programmable
Types E, N, J, K, L
for resistance thermometers
Pt 100 (Standard and Klima range)
Ni 100 (Standard and Klima range)
Temperature compensation
Internal temperature compensation
programmable
supported
External temperature compensation with compensating
box
supported
Compensation for 0 °C reference junction temperature
supported
Technical unit of temperature measurements
Degrees Centigrade

Table of Contents