Loading...
Analog modules
6.8 Analog input module SM 331; AI 2 x 12 bit; (6ES7331-7KB02-0AB0)
S7-300 Automation System Module data
6-66 Manual, 08/2006, A5E00105505-04
Caution
If you have set the measuring range module to the "current" setting and voltage is being
interrogated, the module is destroyed!
Technical data
Technical data
Dimensions and weight
Dimensions W x H x D (mm) 40 x 125 x 117
Weight approx. 250 g
Module-specific data
Isochronous mode supported No
Number of inputs
with resistive transducers
2
1
Cable length
shielded
max. 200 m
max. 50 m at 80 mV and with thermocouples
Voltages, currents, electrical potentials
Rated electronics supply voltage L +
Reverse polarity protection
24 VDC
Yes
Transducer power supply
Supply current
short circuit-proof
max. 60 mA (per channel)
Yes
Constant current for resistive transducers typ. 1.67 mA
Electrical isolation
between channels and the backplane bus
between channels and electronics power supply
not for 2-wire transducers
Yes
Yes
Permissible potential difference
between inputs and M
ANA
(CMV)
at signal = 0 V
between inputs (C
MV
)
between M
ANA
and M
internal
(V
iso
)
typ. DC 2.5 V (> DC 2.3V)
typ. DC 2.5V (> DC 2.3V)
75 VDC / 60 VAC
Isolation test voltage 500 VDC
Current consumption
from the backplane bus
from load voltage L+
max. 50 mA
max. 30 mA (without 2-wire transducer)
Power loss of the module typ. 1.3 W
Formation of analog values
Measuring principle Integrating
Integration/conversion time/resolution (per channel)
programmable
Yes
Integration time in ms
2,5 16
2
/
3
20 100
Basic conversion time, including the integration time in ms
6 34 44 204