Analog modules
6.11 Analog output module SM 332; AO 8 x 12 Bit; (6ES7332-5HF00-0AB0)
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
6-103
Technical data
Voltages, currents, electrical potentials
Rated load voltage L+
Reverse polarity protection
24 VDC
Yes
Electrical isolation
between channels and the backplane bus
between channels and electronics power supply
between channels
between channels and load voltage L+
Yes
Yes
No
Yes
Permissible potential difference
between S- and M
ANA
(CMV)
between M
ANA
and M
internal
(V
ISO
)
3 VDC
75 VDC / 60 VAC
Isolation test voltage 500 VDC
Current consumption
from the backplane bus
from supply voltage L+ (no load)
max. 100 mA
max. 340 mA
Power loss of the module typ. 6.0 W
Formation of analog values
Resolution, including sign
± 10 V; ± 20 mA; 4 mA to 20 mA; 1 V to 5 V
0 V to 10 V; 0 mA to 20 mA;
Conversion time (per channel)
11 bits + sign
12 bits max. 0.8 ms
Settling time
with resistive load
with capacitive load
with inductive load
0.2 ms
3.3 ms
0.5 ms (1 mH)
3.3 ms (10 mH)
Noise suppression, error limits
Crosstalk between outputs
> 40 dB
Operational limit (across the temperature range, relative to output range)
Voltage output
Current output
± 0,5 %
± 0,6 %
Basic error limit (operational error limit at 25 °C, relative to output range)
Output voltage
Output current
Temperature error (relative to output range)
Linearity error (relative to output range)
Repetition accuracy (in transient state at 25 °C, relative to
output range)
Output ripple; bandwidth 0 kHz to 50 kHz (relative to output
range)
± 0,4 %
± 0,5 %
± 0.002 %/K
+ 0,05 %
± 0,05 %
± 0,05 %
Status, interrupts, diagnostics
Interrupts
Diagnostic interrupt
programmable