EasyManua.ls Logo

Siemens Simatic S7-300 - Page 360

Siemens Simatic S7-300
594 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog modules
6.14 Analog output module SM 332; AO 2 x 12 Bit; (6ES7332-5HB01-0AB0)
S7-300 Automation System Module data
6-126 Manual, 08/2006, A5E00105505-04
Technical data
Number of outputs 2
Cable length
shielded
max. 200 m
Voltages, currents, electrical potentials
Rated load voltage L+
Reverse polarity protection
24 VDC
Yes
Electrical isolation
between channels and the backplane bus
between channels and electronics power supply
between channels
between channels and load voltage L+
Yes
Yes
No
Yes
Permissible potential difference
between S- and M
ANA
(CMV)
between M
ANA
and M
internal
(V
iso
)
3 VDC
75 VDC / 60 VAC
Isolation test voltage 500 VDC
Current consumption
from the backplane bus
from load voltage L+ (no-load)
max. 60 mA
max. 135 mA
Power loss of the module typ. 3 W
Formation of analog values
Resolution (including overshoot range)
± 10 V; ± 20 mA;
4 mA to 20 mA; 1 V to 5 V
0 V to 10 V; 0 mA to 20 mA
11 bits + sign
12 bits
Conversion time (per channel) max. 0.8 ms
Settling time
with resistive load
with capacitive load
with inductive load
0.2 ms
3.3 ms
0.5 ms (1 mH)
3.3 ms (10 mH)
Noise suppression, error limits
Crosstalk between outputs > 40 dB
Operational limit (across the temperature range, relative to output range)
Voltage output
Current output
± 0,5 %
± 0,6 %
Basic error limit (operational error limit at 25°, relative to output range)
Voltage output
Current output
± 0,4 %
± 0,5 %
Temperature error (relative to output range) ± 0.002 %/K
Linearity error (relative to output range) ± 0,05 %
Repetition accuracy (in transient state at 25 °C, relative to output
range)
± 0,05 %
Output ripple; range 0 Hz to 50 kHz (relative to output range) ± 0,05 %

Table of Contents