Principles of analog modules
5.1 Representation of the values for analog input channels
S7-300 Module data
266 Manual, 06/2017, A5E00105505-AJ
Representation of the analog values of resistive transducers
Table 5- 10 Representation of the analog values of 6 kΩ; 10 kΩ and from 150 Ω to 600 Ω resistive transducers
Resistive transducer range
32767 7FFF 7.111 kΩ 11.852 kΩ 177.77 Ω 355.54 Ω 711.09 Ω Overflow
Overshoot range
Rated range
(negative values are physically impossible)
Representation of analog values for resistance thermometers Pt x00 and Pt x00 GOST (0.003850)
standard
Table 5- 11 Representation of analog values for resistance thermometers PT 100, 200, 500,1000 and PT 10, 50,100, 500
GOST (0.003850) standard
Pt x00
Standard /
GOST in °C
(1 digit =
0.1°C)
Pt x00
Standard/
GOST in °F
(1 digit =
0.1 °F)
Pt x00
Standard/
GOST in K
(1 digit =
0.1 K)
H
H
H
1000.0
:
10000
:
2710
H
:
1832.0
:
18320
:
4790
H
:
1273.2
:
12732
:
31BC
H
:
Overshoot
range
850.0
:
8500
:
2134
H
:
H
1562.0
:
15620
:
3D04
H
:
H
1123.2
:
11232
:
2BE0
H
:
H
Rated range
-200.1
:
-2001
:
F82F
H
:
-328.1
:
-3281
:
F32F
H
:
73.1
:
731
:
2DB
H
:
Undershoot
range
H
H
H