Principles of analog modules
5.1 Representation of the values for analog input channels
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
267
Representation of the analog values of Pt x00 GOST (0.003910) standard resistance thermometers
Table 5- 12 Representation of the analog values of Pt 10, 50, 100, 500 GOST (0.003910) standard resistance thermome-
ters
Pt x00 GOST
Standard in °C
(1 digit =
0.1°C)
Pt x00 GOST
Standard in
°F (1 digit =
0.1 °F)
1295.0
:
1100.1
12950
:
11001
3296
H
:
2AF9
H
2363.0
:
2012.1
23630
:
20121
5CE4
H
:
4E99
H
Overshoot range
1100.0
:
11000
:
2AF8
H
:
H
2012.0
:
20120
:
4E98
H
:
H
Rated range
-260.1
:
-2601
:
F5D7
H
:
-436.1
:
-4361
:
EEF7
H
:
Undershoot range
H
H
Representation of analog values for Pt x00 and Pt x0 GOST (0.003850 and 0.003910) climatic
resistance thermometers
Table 5- 13 Representation of analog values for Pt 100, 200, 500,1000 and Pt 10, 50, 100, 500 GOST (0.003850 and
0.003910) climatic resistance thermometers
Pt x00 climat-
ic/GOST in °C
(1 digit = 0.01
°C)
Pt x00
climat-
ic/GOST in
°F (1 digit =
0.01 °F)
155.00
:
15500
:
3C8C
H
:
H
311.00
:
31100
:
797C
H
:
H
Overshoot range
130.00
:
13000
:
32C8
H
:
266.00
:
26600
:
67E8
H
:
Rated range
-120.01
:
-12001
:
D11F
H
:
H
-184.01
:
-18401
:
B81F
H
:
H
Undershoot range
H
H