Principles of analog modules
5.1 Representation of the values for analog input channels
S7-300 Module data
268 Manual, 06/2017, A5E00105505-AJ
Representation of the analog values of Ni x00 Standard resistance thermometers
Table 5- 14 Representation of the analog values of Ni100, 120, 200, 500, 1000 and
LG-Ni 1000 resistance thermometers
Ni x00
Standard
in °C (1 digit
= 0.1°C)
Ni x00
Standard in
°F (1 digit =
0.1 °F)
Ni x00
standard
in K (1 digit
= 0.1 K)
295.0
:
250.1
2950
:
2501
B86
H
:
9C5
H
563.0
:
482.1
5630
:
4821
15FE
H
:
12D5
H
568.2
:
523.3
5682
:
5233
1632
H
:
1471
H
Overshoot
range
250.0
:
2500
:
9C4
H
:
H
482.0
:
4820
:
12D4
H
:
H
523.2
:
5232
:
1470
H
:
H
Rated range
-60.1
:
-601
:
FDA7
H
:
-76.1
:
-761
:
FD07
H
:
213.1
:
2131
:
853
H
:
Undershoot
range
H
H
H
Representation of the analog values of Ni x00 climate resistance thermometers
The following table shows the analog values for the resistance thermometer Nix00 Climatic
for all analog input modules.
Exceptions:
● Analog input module AI 8x12-bit; 6ES7331-7KF02-0AB0
● Analog input module AI 2x12-bit; 6ES7331-7KB02-0AB0
There is no overrange for these analog input modules. Overflow begins at 240 °C and is
encoded with 7FFF
H
.