Principles of analog modules
5.1 Representation of the values for analog input channels
S7-300 Module data
270 Manual, 06/2017, A5E00105505-AJ
Representation of the analog values of Ni 100 GOST Klima resistance thermometers
Table 5- 17 Representation of the analog values of Ni 100 GOST Klima resistance thermometers
Ni 100
GOST
Klima in °C
(1 digit =
0.1°C)
Units
Ni 100
GOST Kli-
ma in °F (1
digit = 0.1
°F)
Units
Range
dec
hex
dec
hex
> 212.40
32767
7FFF
H
> 327.66
32767
7FFF
H
Overflow
212.40
:
180.01
21240
:
18001
52F8
H
:
4651
H
327.66
:
280.01
32766
:
28001
7FFE
H
:
6D61
H
Overshoot range
180.00
:
-60.00
18000
:
-6000
4650
H
:
E890
H
280.00
:
-76.00
28000
:
-7600
6D60
H
:
E250
H
Rated range
-60.01
:
-105.00
-6001
:
-10500
E88F
H
:
D6FC
H
-76.01
:
-157.00
-7601
:
-15700
E24F
H
:
C2AC
H
Undershoot range
< - 105.00
-32768
8000
H
< - 157.00
-32768
8000
H
Underflow
Representation of the analog values for Cu 10 standard resistance thermometers
Table 5- 18 Representation of the analog values for Cu 10 standard resistance thermometers
Cu 10 stan-
dard in °C
(1 digit =
0.01 °C)
Units
Cu 10 stan-
dard in °F
(1 digit =
0.01 °F)
Units
Cu 10 stan-
dard in K (1
digit = 0.01
K)
Units
Range
dec
hex
dec
hex
dec
hex
> 312.0
32767
7FFF
H
> 593.6
32767
7FFF
H
> 585.2
32767
7FFF
H
Overflow
312.0
:
260.1
3120
:
2601
C30
H
:
A29
H
593.6
:
500.1
5936
:
5001
1730
H
:
12D5
H
585.2
:
533.3
5852
:
5333
16DC
H
:
14D5
H
Overshoot
range
260.0
:
-200.0
2600
:
-2000
A28
H
:
F830
H
500.0
:
-328.0
5000
:
-3280
1389
H
:
F330
H
533.2
:
73.2
5332
:
732
14D4
H
:
2DC
H
Rated range
-200.1
:
-240.0
-2001
:
-2400
F82F
H
:
F6A0
H
-328.1
:
-400.0
-3281
:
-4000
F32F
H
:
F060
H
73.1
:
33.2
731
:
332
2DB
H
:
14C
H
Undershoot
range
< - 240.0
-32768
8000
H
< - 400.0
-32768
8000
H
< 33.2
32768
8000
H
Underflow

Table of Contents

Other manuals for Siemens SIMATIC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC and is the answer not in the manual?

Siemens SIMATIC Specifications

General IconGeneral
Product type designationSIMATIC
CPUVaries by model
MemoryVaries by model
Input/OutputVaries by model
CommunicationVaries by model
Programming LanguageSTEP 7
Operating Temperature0°C to 60°C (varies by model)
Protection ClassIP20
CategoryProgrammable Logic Controller (PLC)