Description of the blocks
4.6 Block for timestamping MMLog
SIMOCODE pro PCS 7 Library V9.0
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
185
The error buffer is available for SIMOCODE pro C / S / V PROFIBUS and PROFINET.
The error buffer contains the tripping events and events that a SIMOCODE pro device has
saved.
A maximum of 21 messages are recorded and displayed in the Logbook view (Page 195).
Each message contains the following attributes:
Output
to
Number of the message Number of the message
Output LogTm1 to LogTm21 Operating hours of the
Real-time stamp
1
2
Output EnCktCls / EnCktOpn
Output ClsTmStmp / OpnTmStmp
Date and real time are logged, if there is a valid time that has been synchronized via an NTP clock
or set manually with SIMOCODE ES.
2
When using DM-F expansion modules with SIMOCODE pro V.
The values are read from the SIMOCODE pro device with the "RDREC" function. This
information is written to the output parameters.
Read ac-
cess/write
access
3 DS76 R 193 Time stamp for tripping
No Yes
4 DS77 R 193 Time stamp for events
No Yes
Note
The user can suppress the reading of these datarecords by selecting the Feature.Bit26 = 1.
In that case, the data is not read from the device. Also the Logbook view button will be
disabled at the Faceplates.