Description of the blocks
4.6 Block for timestamping MMLog
SIMOCODE pro PCS 7 Library V9.0
192 Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
4.6.7
Driver generator
The "Generate Module Driver" function automatically inserts the MMLog block into the
following organization blocks within the run sequence:
OB40 (process alarm)
OB100 (warm restart)
The
DAddr input is parameterized via the information from the HW Config.
4.6.8
Start-up characteristics
In OB100, the identifier for "Start up" is entered in output OMODE (OMODE = 16#xx01xxxx).
The alarm messages are suppressed in the OB100 for the
RunUpCyc no. of times.
Acknowledge the errors
GrpErr, RackF_Act, ModF_Act, Rack1Err, and Rack2Err.
4.6.9
Status information
The status information is communicated to WinCC for display in the faceplates.
Table 4- 91 Status information – MMLog
Status1
Bit
Description
0
Occupied
1 BatchEn
2
SIMOCODE Device Class
3
1 = Oos Mode
4
OosLi Active
5 0 = Default read logbook
1 =Suppress logbook
6 0 = On mode
1 = Local mode
7
Message Lock
8
Time stamp Active
9
Logbook error 1 Type
10
Logbook error 2 Type
11
Logbook error 3 Type
12
Logbook error 4 Type
13
Logbook error 5 Type
14
Logbook error 6 Type
15
Logbook error 7 Type
16
Logbook error 8 Type
17
Logbook error 9 Type

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro PCS 7 and is the answer not in the manual?

Siemens SIMOCODE pro PCS 7 Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro PCS 7
CategoryControl Unit
LanguageEnglish

Related product manuals