4.1.10.14
Activate fault status for external control system fault
Number of the Feature bit: 18
Feature bit purpose
Specify whether the block should switch to the error state at an external process control error
CSF =1.
The default setting is 0.
Bit = 0:
Block does not go to error state with process control error CSF = 1.
Bit = 1:
Activated: Block goes to error state with process control error CSF = 1.
4.1.10.15
Reset even in locked state
Number of the Feature bit: 19
Feature bit purpose
You can specify if it is possible to perform a reset with an active "Protection" or "Motor
protection" type interlock. This can be used, for example, to reset hardware interlocks.
The default setting is 0.
Bit = 0:
No reset is possible with a "Protection" type interlock or with active motor protection.
Bit = 1:
Reset is possible with a "Protection" type interlock or with active motor protection.
4.1.10.16
Disable Feedback Tracking LocalSetting 2 & 4
Number of the Feature bit: 20
Feature bit purpose
To disable the tracking of feedback signals in the "Local" mode setting 2 and 4.
The default setting is 0.
Bit = 0:
Calculation of impulse controls in LocalSetting 2 and 4.
Bit = 1:
Disable calculation of impulse controls in LocalSetting 2 and 4.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro PCS 7 and is the answer not in the manual?

Siemens SIMOCODE pro PCS 7 Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro PCS 7
CategoryControl Unit
LanguageEnglish

Related product manuals