Description of the blocks
4.1 Functions for all blocks
SIMOCODE pro PCS 7 Library V9.0
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
85
Bit = 1:
Activated: Tracking of feedback for simulation after the trigger signal and expiration
of the monitoring time (
MonTiDynamic). The feedback signals are generated after expiration of
the monitoring time.
4.1.10.11
Separate monitoring time for stopping the motor
Number of the Feature bit: 13
Feature bit purpose
To activate a separate monitoring time for stopping the motor.
The default setting is 0.
Bit = 0:
A monitoring time for starting and stopping the motor.
Bit = 1:
Separate monitoring time for stopping the motor.
4.1.10.12
Enabling rapid stop via faceplate
Number of the Feature bit: 14
Feature bit purpose
Specify if the OS operator can use rapid stop for the block via the standard view of the
faceplate.
The default setting is 0.
Bit = 0:
The "Rapid stop" button is not visible in the faceplate.
Bit = 1:
The OS operator can use the button for rapid stop.
4.1.10.13
Activate bumpless changeover to automatic mode
Number of the Feature bit: 17
Feature bit purpose
To enable the bumpless switchover from local/manual mode to automatic mode.
The default setting is 0.
Bit = 0:
Bumpless switchover is disabled. You can switch from local/manual mode to
automatic mode at any time.
Bit = 1:
Bumpless switchover from local/manual mode to automatic mode is enabled. A
switchover from local/manual mode to automatic mode is possible if the control settings of
the local/manual mode and automatic modes match. If switchover occurs at a different point
in any time, the "Switchover error" text is indicated on the faceplate.