Signal Cause Remedy
Complete information on the messages is available in the List Manual.
F01611 Defect in a monitoring channel.
Fault value r0949 provides more de‐
tailed information.
The remedy depends on the fault value. The complete list of the fault
values is provided in the List Manual.
0: Stop request from processor 2.
1 999: Fault in data cross-check between processor 1 and process‐
or 2.
Details and remedy: Please refer to the List Manual.
1000: Check (watchdog) timer has expired.
When selecting a safety function, the signal changed too frequently.
The inverter monitors the signal to select a safety function after a signal
change.
If the signal state continues to change in shorter intervals than entered
in p9650, after the time 5 × p9650 the inverter outputs fault F1611:
S
SSS
SSS
6HOHFWVDIHW\
IXQFWLRQ
෪S
)
W
Remedy:
Check the F-DI wiring (contact problems).
Resolve the contact problems or faults at the PROFIBUS master/
PROFINET controller.
The inverter terminates the monitoring and does not signal any faults
if the signal state remains stable before the time 5 × p9650 expires,
longer than p9650:
S
SS
6HOHFWVDIHW\
IXQFWLRQ
෪S
W
1001, 1002: Initialization error, change timer/check timer.
Remedy: Switch off the power supply voltage of the inverter and
switch on again.
2000: Status of the STO selection for the two monitoring channels is
different.
Response to a discrepancy when STO is active (Page 226)
2001: Checkback signal of the safe pulse suppression for the two
monitoring channels is different.
Operation
6.14 List of alarms and faults
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD 321

Table of Contents

Other manuals for Siemens SINAMICS G120C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C and is the answer not in the manual?

Siemens SINAMICS G120C Specifications

General IconGeneral
Communication InterfacesPROFINET, PROFIBUS, USS, Modbus RTU
Protection ClassIP20
Ambient Temperature-10°C to +50°C
Storage Temperature-40°C to +70°C
Power Range0.55 kW to 132 kW
Voltage Range380 V to 480 V
Output Voltage0 V to Supply Voltage
Frequency Range0 Hz to rated output frequency
Control ModesVector control with encoder
ProtectionOverload, overvoltage, undervoltage, short circuit, ground fault
Relative Humidity5% to 95%, non-condensing
AltitudeUp to 2000 m without derating

Related product manuals