Signal Cause Remedy
Complete information on the messages is available in the List Manual.
F01658 PROFIsafe telegram number un‐
suitable
The PROFIsafe telegram number in p60022 is not suitable for the en‐
abled safety functions.
Check the following:
If PROFIsafe is not enabled (p9601.3 = 0), PROFIsafe telegrams
must not be selected in p60022.
If PROFIsafe is enabled (p9601.3 = 1), you must select a
PROFIsafe telegram in p60022.
If transfer of the F-DI via PROFIsafe is selected (p9501.30 = 1),
you must select telegram 900 in p60022.
F01659 Write task for parameter rejected Check the setting of the safety functions.
You can find possible reasons for the message in the List Manual.
F01660 Safety functions not supported Use a Power Module that supports the safety functions.
Restrictions when using safety functions (Page 27)
F01661 Simulation of the safety inputs ac‐
tive
Exit the simulation of the digital inputs of the Control Unit for the F-DI
(p0795).
F01662 Error, internal communications
1. Switch off the Control Unit power supply and then on again.
2. Contact Technical Support if it cannot be acknowledged.
F01663 Copying the SI parameters rejected
1. Set p9700 = 0.
2. Check: p9501 ≠ 0 and/or p9601 ≠ 0.
If this is the case, then correct both parameters.
3. Start the copy function again by entering the corresponding value
into p9700.
F01665 System is defective The inverter has identified a defect:
1. Switch off the Control Unit power supply and then on again.
2. Contact Technical Support if it cannot be acknowledged.
You have not configured the "STO via Power Module terminals" func‐
tion, but you have activated the terminals on the PM240‑2 or
PM240P‑2 Power Module:
1. Set the switch for the fail-safe digital input of the Power Module
(STO_A and STO_B) into the "OFF" position.
A01666,
F01666
Static 1 signal at the F-DI for safe
acknowledgement
Set the signal at the F-DI to acknowledge the safety functions for a
logical 0 signal.
A01669 Unsuitable combination of motor
and power unit.
The ratio between the rated power unit current (r0207[0]) and rated
motor current (p0305) should be greater than 5.
In operation, message C01711 or C30711 can be sporadically output
with values
1041 … 1044.
Use a suitable power unit with a lower power rating or a motor with a
higher power rating.
A01678 Test stop for STO via terminals at
the PM required
The set time (p9661) to monitor the forced checking procedure (test
stop) for the "STO via Power Module terminals" function has been
exceeded.
Deselect the "STO via Power Module terminals" function and then se‐
lect again.
Operation
6.14 List of alarms and faults
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
324 Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD

Table of Contents

Other manuals for Siemens SINAMICS G120C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C and is the answer not in the manual?

Siemens SINAMICS G120C Specifications

General IconGeneral
Communication InterfacesPROFINET, PROFIBUS, USS, Modbus RTU
Protection ClassIP20
Ambient Temperature-10°C to +50°C
Storage Temperature-40°C to +70°C
Power Range0.55 kW to 132 kW
Voltage Range380 V to 480 V
Output Voltage0 V to Supply Voltage
Frequency Range0 Hz to rated output frequency
Control ModesVector control with encoder
ProtectionOverload, overvoltage, undervoltage, short circuit, ground fault
Relative Humidity5% to 95%, non-condensing
AltitudeUp to 2000 m without derating