EasyManua.ls Logo

Siemens SINAMICS S150 - 9.2 Active Infeed functions

Siemens SINAMICS S150
312 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Acceptance test and acceptance report
10.5 Acceptance tests
Safety Integrated
Function Manual, 05/2010, A5E03264275A
303
Trace evaluation:
SLS function with SLS level 1 is active (see bits "deselection SLS", "selection SLS bit 0",
"selection SLS bit 1" and "SLS active", "active SLS level bit 0" and "active SLS level
bit 1")
Drive is accelerated beyond the SLS limit (time axis from approx. -800 ms)
Exceeding of the limit is recognized (time axis 0 ms)
Safety fault is initiated (time axis 0 ms; bit "internal event" is set to 0)
Fault response STOP A is initiated (time axis 0 ms; see bit "STOP A or B active" and
"STO active")
Drive coasts (see red curve of r9714[0])
Note
Small time differences (of the order of 2 to 3 Safety clock cycles (here up to 36 ms)) are
caused by internal calculations and do not present a problem.

Table of Contents

Other manuals for Siemens SINAMICS S150

Related product manuals